CARIMOTechnologies

CAPMAC / CARI-Tune

CARI-Tune · Loop tuning for process plants

Settings your loops can trust.

Find the controllers whose settings are too aggressive. The valve is checked first. Then your engineer gets three new settings for each loop: slow, normal and fast, each with its safety margin, pictures of the predicted response, and a sheet in your controller block's own words.

CARI-Tune includes everything in CARI-Loops, the health check of every loop and valve, and adds the tuning.

  • Valve first, always
  • Three settings, each with its margin
  • Ten settings-sheet styles
  • Proposer and approver on every change
Worked example: reactor temperature loop. Predicted response to a 1 °C set-point step, today and with each new setting
Chart of a reactor temperature loop answering a set-point step: today's setting peaks at 1.74 and swings both ways, while the slow, normal and fast settings settle
Your setting todaySlowNormalFast
The film

Watch the film

3 min 8 s, with captions. Sound on for the narration.

CARI-Tune film
A control screen showing a process value that swings up and down
One tuning job, end to end

From the swing to the signed change.

Choose the balance each loop needs: a calmer answer to set-point moves, a firmer hold against load changes, and a stated safety margin. CARI-Tune gives your team one clear path from the loop that swings to the change that is approved, entered and checked.

It works from the exports your control system already keeps and from two tests your own engineer runs, planned with your operating team. No new sensors. Your engineer enters every setting through your own change procedure.

Tested on our own test plants built to industry practice.

CARI-Tune · one loop, three settings
CARI-Tune screen for one loop: slow, normal and fast settings with gain, integral time and safety margin, an Approve button for each, and two charts
1.74 → 1.36peak after a set-point step, today against Normal (target 1)
497 → 340 stime to settle within 5 %, today against Normal
3 settingsslow, normal, fast, each with its stated safety margin
10 sheet stylesin control systems' own field names and units
A touchscreen controller faceplate with level bars
What you send, what you receive

From a health check to settings you can enter.

CARI-Tune includes the CARI-Loops health check, taking your team from a ranked export to approved tuning settings. The health check grades every loop in your export; the loops that need retuning go straight in.

You send

  • Trend export of the unit. Time, measurement, set point, controller output and mode for each loop, as CSV from your DCS, PLC, SCADA or historian.
  • Current gain, integral time and action. Add them to compare with today; enter them before approval.
  • Your cost of error. Optional; turns health order into money order.
  • Valve stroke test result. Passed or not, run only on the loops graded for retuning.
  • Short loop test file. Steady running, one small step of the controller output, then a few small moves each way. Twelve minutes in the worked example.

You receive

  • One ranked table for the unit. Every loop with its grade and the reason in words.
  • Three settings for each loop to retune. Gain, integral time and stated safety margin (gain margin).
  • Two pictures for each of those loops. Predicted set-point and load responses, beside today's setting.
  • A settings sheet in your system's style. Field names, units and action; CSV and a printable page.
  • A sealed change history. Proposer, approver, old and new settings, and a record code.
A control valve with its positioner on a process line
The valve-first rule

Check the valve. Then tune the loop.

A sticking valve needs valve work, not new settings. So CARI-Tune grades every loop first, and gives settings where the health check and the loop test point to the settings themselves.

01

Find the loop

The built-in health check names the loops that swing and grades the likely cause.

02

Check the valve

Your engineer runs a valve stroke test. A valve that fails is fixed first.

03

Short loop test

One small step of the controller output, then a few small moves each way, run by your engineer.

04

Three settings

Slow, normal and fast, drawn beside the setting you run today.

Grade on screenWhat you get
needs retuningThree settings, two pictures, a settings sheet.
test the valveNo settings. A valve stroke test to run first.
instrument firstNo settings. The transmitter to check.
no problem foundLeft alone. Nothing to tune.
CARI-Tune · loops ranked
Loops ranked by health: one needs retuning, two have no problem found
Worked example

A reactor temperature loop that swings on every move.

The app opens with a worked example from a standard published test plant: a chemical process with reactor loops. Nine hours of routine record, a twelve-minute loop test run by the engineer, and three settings drawn next to today's.

The routine record

Nine hours of reactor temperature against its set point, swinging after each set-point changeController output over the same nine hours

Temperature against its set point, and the controller output, one row every 9 seconds.

The short loop test

Twelve-minute loop test: temperature moving within 0.2 degrees of its set pointController output moved 2 percentage points each way during the test

The controller output moved 2 percentage points each way; the temperature stayed within 0.2 °C of its starting value.

SettingGainIntegral timeSafety marginSet-point peak (1 °C step)Settles within ± 5 % of the step
Today−24450 snot stated1.74497 s
Slow−2.57227 sat least 3.5×1.30529 s
Normal−3.90182 sat least 2.67×1.36340 s
Fast−6.02136 sat least 2×1.49294 s

Predicted temperature response to a 1 °C set-point step

Set-point step response for today's setting and the slow, normal and fast settings

Predicted response, °C, to a load step of 1 % at the process input

Load step response for today's setting and the slow, normal and fast settings
Your setting todaySlowNormalFast

Safety margin here means gain margin: the factor by which the process gain can rise before the predicted response reaches steady cycling. In this example today's setting gives the smallest predicted load bump but swings after a set-point step. Slow gives the lowest peak; Fast gives the smallest load bump of the three new settings and settles soonest. Compare both pictures and choose what the loop needs.

Transmitters with small displays on a process pipe
Your control system's own words

The same setting, in your block's own words.

Pick your controller block. The sheet gives the gain or the proportional band, the integral setting in the block's own units, and the controller action, side by side. Nobody converts by hand at the panel.

Settings-sheet styleGain fieldIntegral fieldGain valueIntegral value
Generic ISA / ideal textbook formKcTi (s/repeat)3.898181.6
Emerson DeltaV PID function blockGAINRESET (s/repeat)3.898181.6
Honeywell Experion / TDC PIDK (gain)T1 (min/repeat)3.8983.027
Yokogawa CENTUM VP PIDP (PB %)I (s)25.66181.6
Siemens PCS 7 CONT_C / PIDConLGAINTI (s)3.898181.6
Rockwell Logix PIDE — Dependent gainsPGainIGain (min/repeat)3.8983.027
Rockwell Logix PIDE — Independent gainsPGain (Kp)IGain (Ki, 1/min)3.8981.288
Foxboro (Schneider) I/A Series PIDAPBAND (%)INT (min/repeat)25.663.027
ABB 800xA PidCC / PidAdvancedGainTi (s)3.898181.6
Generic Reset-rate style (repeats/min)KcReset (repeats/min)3.8980.3303

The Normal setting of the example loop, as the app writes it in each of the ten styles. On every sheet the controller action, direct or reverse, is its own column. A band is 100 divided by the gain, right for a span of 100 units; your engineer confirms the block's span, scaling and action.

CARI-Tune · settings sheet
Settings sheet in a control system's own style, with CSV download and printable page
A control room with process screens
Approvals and change history

Proposer, approver, and a code on the print.

Tuning changes are small to type and large in effect. CARI-Tune treats each one as a controlled change: proposed by one person, approved by another, and kept in the change history.

CARI-Tune · approvals and change history
Approvals with two names and the change history table

Proposer and approver

Different proposer and approver names are required. CARIMO sets up sign-in and approval responsibilities with your team.

Sealed records

Every record is sealed to the one before it. CARI-Tune checks the chain each time it reads the history and reports a failed check.

A code on the print

The printed report records the length of the history and its last record code. Keep the signed report with your change records.

A touchscreen controller showing a bar chart
Monthly re-check and readiness

Check the change. Then keep checking.

After entry, your engineer checks the controller read-back and the loop trend. Then, once a month, add that month's readings: CARI-Tune compares each loop with its own reference months. After a retune, one button starts a fresh set.

CARI-Tune · monthly re-check
Monthly re-check: month by month chips and a health index for two loops, one slower and one valve-like in month six

Two of our own test loops. Verdict words: better, no change, slower, valve-like, worse. Index 100 means as in the loop's own reference months; it is an index, not a percentage.

CARI-Tune · readiness column
Readiness column before an advanced-control step test: an issue found for one loop, nothing found in the routine record for two

Before an advanced-control step test, each loop shows the issue found, or the words “nothing found in the routine record”.

A process vessel with steam rising beside an industrial plant
Working with your team

On your own PC. Under your own change procedure.

Where it runs

On your own PC, opened in a web browser. Your records stay on your PC. CARIMO sets up the app with your team and supports the first unit.

Entered by your engineer

CARI-Tune reads exported files and needs no link to the control system. Your engineer enters each approved setting from the sheet.

Loop types in the app

Flow, level, pressure, temperature, analysis, density, speed and weight. Direct and reverse acting. Whole units at once.

Writing an approved setting into the control system, and automatic retuning as the process drifts, are set up and tested with your team first.

Show us one loop. See three settings.

Start with one loop, or the trend export of a unit. We agree the export, the test plan and the first-loop review with your team.

Request a demo